{{Resource | |||
|name=Unterverteilung | |||
|description=power distribution | |||
|location=WC mit Pissoir | |||
|resource category=Infrastruktur | |||
|ownership=club | |||
|contactnick=ragnar | |||
|use=careful | |||
|broken=notify | |||
|annoying=notify | |||
|has label=No | |||
|preview image=Yes | |||
}} | |||
{{#set:Has maximum power=43470W}} | |||
[[File:Grundriss Strom.png|300px|thumb|right|Warum liegt denn da Strom rum?]] | |||
[[File:Sicherungskasten oben 20121130.jpeg |300px|thumb|right|strace]] | |||
[[File:Sicherungskasten unten 20121130.jpeg|300px|thumb|right|truss]] | |||
Derzeitiger Aufbau unserer Unterverteilung. Im Zweifelsfall natürlich immer nachprüfen/messen. | Derzeitiger Aufbau unserer Unterverteilung. Im Zweifelsfall natürlich immer nachprüfen/messen. | ||
Mit "unbekannt" markierte Automaten sind verbunden, aber aus, und bleiben besser auch aus. "nicht verbunden" sind im Kasten nicht angeschlossen. | Mit "unbekannt" markierte Automaten sind verbunden, aber aus, und bleiben besser auch aus. "nicht verbunden" sind im Kasten nicht angeschlossen. | ||
'''Stand: | Siehe auch: [[Maschinenraum/Strom|Strom im Maschinenraum]] (Schalter befindet sich links unten über dem Hauptschalter und ist beschriftet). | ||
'''Stand: 30.11.2012''' | |||
== Automaten == | |||
Im Sicherungskasten im Hausflur befinden sich drei 50A Schmelzsicherungen, von dort aus geht die Zuleitung zu unserem Kasten. | |||
{| class="wikitable" | {| class="wikitable sortable" | ||
! Nr !! Wat | ! Nr !! L !! Wat !! Type of | ||
|- | |||
| 1 || L1 || WC Herren || Licht, Steckdose | |||
|- | |||
| 2 || L2 || WC Damen || Licht | |||
|- | |||
| 3 || L3 || Transporterraum, Raucherraum, Durchgang || Licht, Steckdose | |||
|- | |||
| 4 || L1 || Serverraum || Licht | |||
|- | |||
| 5 || L2 || Dusche || Licht | |||
|- | |||
| 6 || L3 || Küche + Küchenlager || Licht | |||
|- | |||
| 7 || L1 || Küchenregal || Steckdose | |||
|- | |||
| 8 || L2 || Backofen || Steckdose | |||
|- | |||
| 9 || L3 || Notbeleuchtung Maschinenraum || Licht | |||
|- | |||
| 10 || L1 || Nomspace || Licht | |||
|- | |||
| 11 || L2 || Kabelkanal Treppe, 1. Dose von hinten || Steckdose | |||
|- | |||
| 12 || L3 || || nicht verbunden | |||
|- | |||
| 13 || L1 || Hackcenter Heizung || Steckdose | |||
|- | |||
| 14 || L2 || Nomspace (Mete-Tablet, Dreierdose etc) || Steckdose | |||
|- | |||
| 15 || L3 || Hackcenter Spiegel || Steckdose | |||
|- | |||
| 16 || L1 || Hackcenter Drucker || Steckdose | |||
|- | |||
| 17 || L2 || Tür (Dockstar/Motor) || Steckdose | |||
|- | |||
| 18 || L3 || Treppe links/Garderobe, Bikeshed || | |||
|- | |||
| 19 || L1 || Treppe rechts/Geländer || | |||
|- | |||
| 20 || L2 || Hackcenter Bücherregal || | |||
|- | |||
| 21 || L3 || Lounge Fenster || Steckdose | |||
|- | |||
| 22 || L1 || Kabelkanal lang (Freifunk) || Steckdose | |||
|- | |||
| 23 || L2 || Kabelkanal Treppe, 3. Dose von hinten || Steckdose | |||
|- | |||
| 24 || L3 || Serverraum | |||
|- | |||
| 25 || L1 || Kabelkanal Treppe, 2. Dose von hinten | |||
|- | |||
| 26 || L2 || Kabelkanal lang vorne (falsch mit (X) beschriftet) | |||
|- | |||
| 27 || L3 || Kabelkanal lang || unbekannt | |||
|- | |||
| 28 || L1 || nomspace Decke (Kühlschrank) || Steckdose | |||
|- | |||
| 29 || L2 || || nicht verbunden | |||
|- | |||
| 30 || L3 || || nicht verbunden | |||
|- | |||
| 31 || L1 || || nicht verbunden | |||
|- | |||
| 32 || L2 || Deckenbeleuchtung Hauptraum + 12V Trafo || Licht | |||
|- | |||
| 33 || || || unbekannt | |||
|- | |||
| 34 || || || unbekannt | |||
|- | |||
| 35 || || || nicht verbunden | |||
|- | |||
| 36 || || || nicht verbunden | |||
|- | |||
| 37 || || || nicht verbunden | |||
|- | |- | ||
| | | 38 || L1 | ||
| rowspan="3" | Durchlauferhitzer | |||
| rowspan="3" | | |||
|- | |- | ||
| | | 39 || L2 | ||
|- | |- | ||
| | | 40 || L3 | ||
|} | |||
== FIs == | |||
Haben wir. Sind regelmäßig zu testen. <del>FI 2 sollte nur in einer scheduled Downtime des Serverraums getestet werden.</del> | |||
=== FI Testdoku === | |||
{| class="wikitable" | |||
! Datum !! FI 1 !! FI 2 !! [[Maschinenraum/Strom|FI 3]] !! Kommentar | |||
|- | |- | ||
| | | 27.08.2014 || X || X || || | ||
|- | |- | ||
| | | 28.10.2014 || X || || || | ||
|- | |- | ||
| | | 23.11.2014 || X || X || X || Test mit einem BEHA Unitest 0100-Expert plus - die Auslösezeit war in Ordnung | ||
|- | |- | ||
| | | 05.02.2016 || || X || || Kaputtes Netzteil \o/ | ||
|} | |||
== Relais == | |||
Oben rechts direkt neben dem 12V-Trafo (dieser liefert die Steuerspannung). Sowohl der Trafo als auch der geschaltete Strom liegt an Sicherung 32. | |||
Relais 1 klebt und geht nicht zuverlässig aus. | |||
{| class="wikitable" | |||
! Nr !! Wtf | |||
|- | |- | ||
| | | 1 || - | ||
|- | |- | ||
| | | 2 || - | ||
|- | |- | ||
| | | 3 || - | ||
|- | |- | ||
| | | 4 || Kabelkanal Hackcenter (unbekannt, nichts angeschlossen) | ||
|- | |- | ||
| | | 5 || Beleuchtung Lounge (grüne LEDs) | ||
|} | |||
== Flukso == | |||
{{H|flukso}} steht über dem Sicherungskasten und wird über den 12V-Trafo versorgt. Die Messklemmen hängen an der Zuleitung vom Haus-Sicherungskasten im Flur, vor unserem Hauptschalter und vor der Verzweigung zum [[Maschinenraum/Strom|Maschinenraum]]. | |||
Es handelt sich um Hallsensoren, ein Betrieb ohne angeschlossenen / eingeschalteten Flukso ist also ungefährlich. | |||
== Stromverbrauch nach Sicherung == | |||
Bei unbelastetem Chaosdorf. | |||
{| class="wikitable sortable" | |||
! Nr !! L !! Datum !! Verbrauch [W] !! Kommentar | |||
|- | |- | ||
| | | 1 || L1 || 2013-12-07 || 0 || Klo. Licht und Lüfter sind 250W | ||
|- | |- | ||
| | | 2 || L2 || 2013-12-07 || 0 || Klo | ||
|- | |- | ||
| | | 3 || L3 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | 4 || L1 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | 5 || L2 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | 6 || L3 || 2013-12-07 || 0 || Licht 120W | ||
|- | |- | ||
| | | 7 || L1 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | 8 || L2 || 2013-12-07 || 3 || | ||
|- | |- | ||
| | | 9 || L3 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | 11 || L2 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | 12 || L3 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | 13 || L1 || 2013-12-07 || 60 || Switch 25W, Licht Tisch 5W, Makerbot 5W, NES Bildschirm 5W, NES 20W | ||
|- | |- | ||
| | | 14 || L2 || 2013-12-07 || 5 || Nur mete-Tablet? | ||
|- | |- | ||
| | | 15 || L3 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | 16 || L1 || 2013-12-07 || 90 || Steckerleiste links vom Drucker 10W, RIP 20W, Drucker 60W (im Poweroff?! -> ausgesteckt) | ||
|- | |- | ||
| | | 17 || L2 || 2013-12-07 || 45 || | ||
|- | |- | ||
| | | 18 || L3 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | 19 || L1 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | 20 || L2 || 2013-12-07 || 70 || Dashpi Display 20W (Bild anzeigend), Fernseher softoff 1W (30VA?), Leucht+Raspi+Tisch 20W | ||
|- | |- | ||
| | | 21 || L3 || 2013-12-07 || 10 || | ||
|- | |- | ||
| | | 22 || L1 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | 23 || L2 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | 25 || L1 || 2013-12-07 || 0 || | ||
|- | |- | ||
| | | MR || || 2013-12-07 || 0 || | ||
|- | |- | ||
|} | |} | ||
In Summe 280. Dazu unbekannter Verbrauch von Kühlschränken. | |||
Serverraum USV Eingang: 190W/245VA |
Latest revision as of 18:54, 1 July 2020
Unterverteilung | |
---|---|
power distribution | |
Ort | WC mit Pissoir |
Besitzstatus | Club-Eigentum |
Kontakt | ragnar |
Benutzung | vorsichtig |
Label | Bitte ausdrucken |
Derzeitiger Aufbau unserer Unterverteilung. Im Zweifelsfall natürlich immer nachprüfen/messen.
Mit "unbekannt" markierte Automaten sind verbunden, aber aus, und bleiben besser auch aus. "nicht verbunden" sind im Kasten nicht angeschlossen.
Siehe auch: Strom im Maschinenraum (Schalter befindet sich links unten über dem Hauptschalter und ist beschriftet).
Stand: 30.11.2012
Automaten[edit source]
Im Sicherungskasten im Hausflur befinden sich drei 50A Schmelzsicherungen, von dort aus geht die Zuleitung zu unserem Kasten.
Nr | L | Wat | Type of |
---|---|---|---|
1 | L1 | WC Herren | Licht, Steckdose |
2 | L2 | WC Damen | Licht |
3 | L3 | Transporterraum, Raucherraum, Durchgang | Licht, Steckdose |
4 | L1 | Serverraum | Licht |
5 | L2 | Dusche | Licht |
6 | L3 | Küche + Küchenlager | Licht |
7 | L1 | Küchenregal | Steckdose |
8 | L2 | Backofen | Steckdose |
9 | L3 | Notbeleuchtung Maschinenraum | Licht |
10 | L1 | Nomspace | Licht |
11 | L2 | Kabelkanal Treppe, 1. Dose von hinten | Steckdose |
12 | L3 | nicht verbunden | |
13 | L1 | Hackcenter Heizung | Steckdose |
14 | L2 | Nomspace (Mete-Tablet, Dreierdose etc) | Steckdose |
15 | L3 | Hackcenter Spiegel | Steckdose |
16 | L1 | Hackcenter Drucker | Steckdose |
17 | L2 | Tür (Dockstar/Motor) | Steckdose |
18 | L3 | Treppe links/Garderobe, Bikeshed | |
19 | L1 | Treppe rechts/Geländer | |
20 | L2 | Hackcenter Bücherregal | |
21 | L3 | Lounge Fenster | Steckdose |
22 | L1 | Kabelkanal lang (Freifunk) | Steckdose |
23 | L2 | Kabelkanal Treppe, 3. Dose von hinten | Steckdose |
24 | L3 | Serverraum | |
25 | L1 | Kabelkanal Treppe, 2. Dose von hinten | |
26 | L2 | Kabelkanal lang vorne (falsch mit (X) beschriftet) | |
27 | L3 | Kabelkanal lang | unbekannt |
28 | L1 | nomspace Decke (Kühlschrank) | Steckdose |
29 | L2 | nicht verbunden | |
30 | L3 | nicht verbunden | |
31 | L1 | nicht verbunden | |
32 | L2 | Deckenbeleuchtung Hauptraum + 12V Trafo | Licht |
33 | unbekannt | ||
34 | unbekannt | ||
35 | nicht verbunden | ||
36 | nicht verbunden | ||
37 | nicht verbunden | ||
38 | L1 | Durchlauferhitzer | |
39 | L2 | ||
40 | L3 |
FIs[edit source]
Haben wir. Sind regelmäßig zu testen. FI 2 sollte nur in einer scheduled Downtime des Serverraums getestet werden.
FI Testdoku[edit source]
Datum | FI 1 | FI 2 | FI 3 | Kommentar |
---|---|---|---|---|
27.08.2014 | X | X | ||
28.10.2014 | X | |||
23.11.2014 | X | X | X | Test mit einem BEHA Unitest 0100-Expert plus - die Auslösezeit war in Ordnung |
05.02.2016 | X | Kaputtes Netzteil \o/ |
Relais[edit source]
Oben rechts direkt neben dem 12V-Trafo (dieser liefert die Steuerspannung). Sowohl der Trafo als auch der geschaltete Strom liegt an Sicherung 32.
Relais 1 klebt und geht nicht zuverlässig aus.
Nr | Wtf |
---|---|
1 | - |
2 | - |
3 | - |
4 | Kabelkanal Hackcenter (unbekannt, nichts angeschlossen) |
5 | Beleuchtung Lounge (grüne LEDs) |
Flukso[edit source]
flukso steht über dem Sicherungskasten und wird über den 12V-Trafo versorgt. Die Messklemmen hängen an der Zuleitung vom Haus-Sicherungskasten im Flur, vor unserem Hauptschalter und vor der Verzweigung zum Maschinenraum.
Es handelt sich um Hallsensoren, ein Betrieb ohne angeschlossenen / eingeschalteten Flukso ist also ungefährlich.
Stromverbrauch nach Sicherung[edit source]
Bei unbelastetem Chaosdorf.
Nr | L | Datum | Verbrauch [W] | Kommentar |
---|---|---|---|---|
1 | L1 | 2013-12-07 | 0 | Klo. Licht und Lüfter sind 250W |
2 | L2 | 2013-12-07 | 0 | Klo |
3 | L3 | 2013-12-07 | 0 | |
4 | L1 | 2013-12-07 | 0 | |
5 | L2 | 2013-12-07 | 0 | |
6 | L3 | 2013-12-07 | 0 | Licht 120W |
7 | L1 | 2013-12-07 | 0 | |
8 | L2 | 2013-12-07 | 3 | |
9 | L3 | 2013-12-07 | 0 | |
11 | L2 | 2013-12-07 | 0 | |
12 | L3 | 2013-12-07 | 0 | |
13 | L1 | 2013-12-07 | 60 | Switch 25W, Licht Tisch 5W, Makerbot 5W, NES Bildschirm 5W, NES 20W |
14 | L2 | 2013-12-07 | 5 | Nur mete-Tablet? |
15 | L3 | 2013-12-07 | 0 | |
16 | L1 | 2013-12-07 | 90 | Steckerleiste links vom Drucker 10W, RIP 20W, Drucker 60W (im Poweroff?! -> ausgesteckt) |
17 | L2 | 2013-12-07 | 45 | |
18 | L3 | 2013-12-07 | 0 | |
19 | L1 | 2013-12-07 | 0 | |
20 | L2 | 2013-12-07 | 70 | Dashpi Display 20W (Bild anzeigend), Fernseher softoff 1W (30VA?), Leucht+Raspi+Tisch 20W |
21 | L3 | 2013-12-07 | 10 | |
22 | L1 | 2013-12-07 | 0 | |
23 | L2 | 2013-12-07 | 0 | |
25 | L1 | 2013-12-07 | 0 | |
MR | 2013-12-07 | 0 |
In Summe 280. Dazu unbekannter Verbrauch von Kühlschränken.
Serverraum USV Eingang: 190W/245VA