{| class="wikitable" | {| class="wikitable" | ||
! colspan=" | ! colspan="2"| Data register address !! colspan="4"| Register Description | ||
|- | |- | ||
| | | highByte || lowByte || Description || unit || Format || Mode | ||
|- | |- | ||
| 00 || 00 || A phase voltage || V || Floating point || Read-only | |||
|- | |- | ||
| 00 || 02 || B phase voltage || V || Floating point || Read-only | |||
|- | |- | ||
| 00 || 04 || C phase voltage || V || Floating point || Read-only | |||
|- | |- | ||
| 00 || 08 || A line current || A || Floating point || Read-only | |||
|- | |- | ||
| 00 || 0A || B line current || A || Floating point || Read-only | |||
|- | |- | ||
| 00 || 0C || C line current || A || Floating point || Read-only | |||
|- | |- | ||
| 00 || 10 || Total active power || KWh || Floating point || Read-only | |||
|- | |- | ||
| 00 || 12 || A phase active power || KWh || Floating point || Read-only | |||
|- | |- | ||
| 00 || 14 || B phase active power || KWh || Floating point || Read-only | |||
|- | |- | ||
| 00 || 16 || C phase active power || KWh || Floating point || Read-only | |||
|- | |- | ||
| 00 || 18 || Total reactive power || KWh || Floating point || Read-only | |||
|- | |- | ||
| 00 || 1A || A phase reactive power || Var || Floating point || Read-only | |||
|- | |- | ||
| 00 || 1C || B phase areactive power || Var || Floating point || Read-only | |||
|- | |- | ||
| 00 || 1E || C phase reactive power || Var || Floating point || Read-only | |||
|- | |- | ||
| 00 || 2A || A phase power factor || || Floating point || Read-only | |||
|- | |- | ||
| 00 || 2E || B phase power factor || || Floating point || Read-only | |||
|- | |- | ||
| 00 || 2C || C phase power factor || || Floating point || Read-only | |||
|- | |- | ||
| 00 || 36 || frequency || frequency || Floating point || Read-only | |||
|- | |- | ||
| 01 || 00 || Total active electricity power || KWh || Floating point || Read-only | |||
|- | |- | ||
| 04 || 00 || Total reactive electricity power|| KWh || Floating point || Read-only | |||
|- | |- | ||
|} | |} | ||
Line 307: | Line 307: | ||
! Data !! Detailed description | ! Data !! Detailed description | ||
|- | |- | ||
| 0x01 || Instrument address | | 0x01 || Instrument address | ||
|- | |- | ||
| 0x03 || Function code, read parameter register | | 0x03 || Function code, read parameter register | ||
|- | |- | ||
| 0x00 0x08 || reading the data from the 00 08 meter internal register address | | 0x00 0x08 || reading the data from the 00 08 meter internal register address |